Product Overview: Fluke 1663 Multi-Function Installation Tester
Fluke 1663 Multi-Function Installation Tester for Hardworking Professionals
The Fluke 1663 Installation Tester offers the full range of features and advanced measurement capabilities required by professional installers. It is compact and lightweight (less than 1.3 kg), with a padded backpack and belt for easy portability. The tester is intuitive and easy for skilled workers of all levels to master, and can be put to use immediately to carry out tests quickly and efficiently in accordance with all local regulations. Other features include an on/off switching auto-start function for RCD and loop testing and a self-test function that saves you time and gives you confidence in your results.
Testing of electric vehicle charging post RCD A-EV or RDC-DD type DC protection devices
The tester tests electric vehicle charging post DC protection devices using the RCD Type B (Smooth DC Current) VAR mode, which is based on the IEC 62955 standard, and generates test currents (6/60/200 mA and <2 to 6 mA ramps) for either RCD Type A-EV or RDC-DD devices. This makes it quick and easy to test the 6 mA DC monitor attached to the charging post and can be used in conjunction with the Fluke FEV100 or FEV300.
software compatibility
Compatible with Fluke's TruTest™ software, the Fluke 1663 lets you say goodbye to the traditional hassles of electrical system data management and reporting. Whether you're testing fixed-wire devices or electrical appliances in the office, verifying repairs in the shop, or performing annual inspections, proper data management is critical to generating easy-to-understand reports for your customers, and TruTest™ software makes it easy to quickly and easily import measurements directly from your test instrument, manage files transferred from your instrument, or manually enter data as needed.
Other useful features:
- Check wiring polarity to detect a disconnected zero wire
- Measurement of insulation resistance as well as loop and line resistance
- Z-max memory with loop test for easy evaluation of highest loop test values
- Equipped with a unique zeroing adapter for fast, reliable, and accurate compensation of test pens and power cords
- Measurement of motor windings using on-off test
- Calculation of the Expected Earth Fault Current (PEFC/IK) and Expected Short Circuit Current (PSC/IK)
- Measurement of RCD switching time and trip level (ramp test)
- Simultaneous measurement of trip time and current for RCD A and AC types in one test
- Measuring RCD Variable Current
- Provides automated RCD test sequences
- Includes phase sequence indicator
- Safety class CAT III 500 V, CAT IV 300 V
Product Specification: Fluke 1663 Multi-Function Installation Tester
Specifications: Fluke 1663 and 1664 FC Multi-Function Installation Testers
| AC Voltage Measurement | ||
| range (of scales or measuring equipment) | 500 V | |
| resolution (of a photo) | 0.1 V | |
| Accuracy (45 Hz - 66 Hz) | 0.8% + 3 | |
| Input Impedance | 360 kΩ | |
| overload protection | 660 V rms | |
| Turn-On-Line Test (RLO) | ||
| Range (automatic) | 20 Ω / 200 Ω / 2000 Ω | |
| resolution (of a photo) | 0.01 Ω / 0.1 Ω / 1 Ω | |
| open circuit voltage | >4 V | |
| Insulation Resistance Measurement (RISO) | ||
| test voltage | 50-100-250-500-1000 V | |
| Test voltage accuracy (at rated test current) | +10%/-0% | |
| test voltage | 50 V 100 V 250 V 500 V 1000 V |
|
| Insulation resistance range | 20 MΩ / 50 MΩ 20 MΩ / 100 MΩ 20 MΩ / 200 MΩ 20 MΩ / 200 MΩ / 500 MΩ 20 MΩ / 200 MΩ / 1000 MΩ |
|
| resolution (of a photo) | 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ |
|
| Test Current | 1 mA @ 50 kΩ 1 mA @ 100 kΩ 1 mA @ 250 kΩ 1 mA @ 500 kΩ 1 mA @ 1 MΩ |
|
| Loop and Line Impedance (ZI) | ||
| range (of scales or measuring equipment) | 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω | |
| resolution (of a photo) | 0.001 Ω/ 0.01 Ω/ 0.1 Ω/1 Ω | |
| Expected Ground Fault Current, PSC Test | ||
| range (of scales or measuring equipment) | 1000 A / 10 kA (50 kA) | |
| resolution (of a photo) | 1 A / 0.1 kA | |
| count | The Expected Ground Fault Current (PEFC) or Expected Short Circuit Current (PSC) is determined by dividing the measured supply voltage by the measured loop (L-PE) resistance or line (L-N) resistance, respectively. | |
| RCD Test, RCD Type Measured | ||
| RCD Type | AC¹ G², S³ |
|
| 1663 Model | A4, AC¹, G², S³ | |
| 1664 FC Models | A, AC, B5, S | |
| marginal notes | ¹Corresponds to AC ² General purpose, no delay ³ time delay ⁴ Corresponding pulse signal ⁵ corresponds to a smooth DC signal |
|
| Trip Speed Test (ΔT) | ||
| Current setting¹ | 10-30-100-300-500-1000 mA - VAR 10-30-100 mA |
|
| factor | x ½, x 1 x 5 VAR Mode Type B - 6, 60, 200 mA |
|
| Measurement range | RCD G-Type | 310 ms 50 ms |
| RCD S-Type | 510 ms 160 ms |
|
| EV / RDC-DD | 6 mA - 10s 60 mA - 0.3s 200 mA - 0.1s |
|
| marginal notes | ¹1000 mA AC models only 700 mA max, Type A in VAR mode The VAR mode of the RCD Type B (Smooth DC Current) generates test currents (6/60/200 mA and <2 to 6 mA ramps) for use with the RCD Type A-EV or RDC-DD according to IEC 62955. |
|
| RCD/FI Trip Current Measurement/Ramp Test (IΔN) | ||
| Current range | 30% to 110%¹ for RCD rated current <2 mA to 6 mA Smooth DC³ |
|
| pacemaker | 10%² of IΔN Linear increase within 30 s |
|
| Holding time | RCD G-Type | 300 ms/step |
| RCD S-Type | 500 ms/step | |
| Measurement accuracy | ±5% | |
| Specified trip current range (EN 61008-1) | AC Models 50% through 100% Type A (>10 mA) for 35% to 140% Type A (≤10 mA) for 35% to 200% Model B is 50% through 200%. |
|
| marginal notes | Type ¹A (IΔN > 10 mA) for 30% to 150% Type A (IΔN = 10 mA) for 30% through 210% Model B is 20% through 210%. ²B Type 5% ³ For RCD Type A-EV/RDC-DD according to IEC 62955 |
|
| Ground Resistance Test (RE) | ||
| range (of scales or measuring equipment) | 200 Ω / 2000 Ω | |
| resolution (of a photo) | 0.1 Ω / 1Ω | |
| frequency | 128 Hz | |
| output voltage | 25 V | |
| phase sequence indication | ||
| icon (computing) | |
|
| General technical indicators | ||
| Dimensions (L x W x H) | 10 x 25 x 12.5 cm | |
| Weight (with battery) | 1.3 Kg | |
| Battery type and quantity | AA Type, 6 Sections | |
| tightness | IP-40 | |
| safety | Conforms to EN/IEC 61010-1 and EN/IEC 61010-2-034 standards. | |
| overvoltage | CAT III / 500V; CAT IV 300V | |
| performances | EN61557-1 to EN61557-7 and EN61557-10 | |
Model: Fluke 1663 Multi-Function Installation Tester
FLK-1663
Fluke 1663 Multi-Function Installation Tester
Kit Includes:
- 6 AA (IEC LR6) batteries
- C1600 Hard Carrying Case
- Zeroing Adapter
- Heavy Duty Power Cord
- STD Standard Test Pen Kit
- Padded back and waist straps
- Quick Reference Guide
- TP165X Remote Control Probe and Meter Pen
Comprehensive test and measurement service provider-Shenzhen Weike Electronic Technology Co.