Fluke 1760TR Three-Phase Power Quality Recorder
Fluke 1760TR Three-Phase Power Quality Recorder
Fluke 1760TR Three-Phase Power Quality Recorder
Fluke 1760TR Three-Phase Power Quality Recorder

Fluke 1760TR Three-Phase Power Quality Recorder

¥999,999.00

Main characteristics

  • Fully compliant with Class A requirements. Tests performed according to the strict IEC 61000-4-30 Class A international standard
  • GPS time synchronization. Accurately correlate data with events or datasets generated by other tools
  • Flexible and fully configurable thresholds and scale factors. Users can define detailed interference detection and logging criteria to identify specific problems.
  • Uninterruptible power supply (maintained for 40 minutes). No important events are missed - even the onset and end of interruptions and stoppages are recorded, helping to determine the root cause of the problem.
  • 10 MHz, 6000 Vpk Waveform Capture. Even a detailed view of the shortest event can be captured
  • 2 GB data storage. Long-term, detailed and synchronized recording of numerous electrical parameters
  • Comes with a full suite of software. Provides trend graphs in on-line mode for root cause analysis, statistical summaries, written reports and real-time data monitoring.
  • Plug and Play. Allows quick setup with automatic sensor detection; sensors are powered by the logger, no batteries required
  • Sturdy and durable field design. The insulated housing without rotating components and the robust design allow reliable field testing under virtually any conditions.

SKU:Fluke 1760TR Category. Brand.

  
  • Quantity
    • -
    • +
  •    
Inquire about this product

Product Overview: Fluke 1760TR Three-Phase Power Quality Recorder

Meets stringent Class A standards for power quality testing

The Fluke 1760TR three-phase power quality recorder is fully compliant with IEC 61000-4-30 Class A, making it ideal for advanced power quality analysis and harmonized standards testing. Designed to analyze utility and industrial distribution systems in low and medium voltage grids, this power quality monitoring tool allows users the flexibility to customize thresholds, algorithms and measurement options. The 1760 Power Logger captures detailed information on user-selected parameters.

appliance

Detailed interference analysis - Perform fast transient analysis to identify the root cause of equipment failures for future improvements and preventive maintenance. The fast transient option and 6000 V range make it possible to capture very brief pulses (e.g., lightning strikes).

Compliance with level A quality of service requirements - Verify power quality at the inlet. With Class A standard certification, the Fluke 1760 allows for a variety of rigorous verifications.

Event correlation at multiple locations - With GPS time synchronization, users can quickly detect where the first failure occurs (inside or outside the facility).

Galvanic isolation and DC coupling - Allows comprehensive measurements of different electrical energy systems. For example, troubleshooting UPS systems by synchronizing the recording of battery voltage and power output.

Power quality and power load analysis - Evaluate basic power quality prior to installation to ensure compliance with critical system requirements; and Verify power system capacity prior to adding loads.

Four Fluke 1760 models are available.

Product Features Fluke 1760 Base Model Fluke 1760TR Base Model Fluke 1760 Fluke 1760TR
Power quality statistics according to EN50160 - - - -
List of voltage events (voltage dips, surges and interruptions) - - - -
Uninterrupted recording.
input voltage - - - -
amps - - - -
Electrical energy P, Q, S - - - -
power factor - - - -
kWh - - - -
flicker - - - -
disequilibrium - - - -
frequency - - - -
Voltage and current harmonics (up to 50th)/interharmonics - - - -
THD - - - -
power signal (of an electrical device etc) - - - -
trigger record - - - -
Online mode (oscilloscope, transient and event) - - - -
Fast transient analysis up to 10 MHz - -
4, 600V Voltage Probes - -
4 dual range flexible current probes (1000 A / 200 A ac) - -
GPS time synchronization receivers - -
memory (unit) 2 GB flash memory

Product Specifications: Fluke 1760TR Three-Phase Power Quality Recorder

Overview of measurement functions
Statistical assessment Power quality statistics in accordance with EN50160 and DISDIP tables such as ITIC, CEBEMA and ANSI.
Event List Voltage dips, surges and interruptions are detected and stored in the event list. Also, any activated trigger generates an event that is added to this list.
The event list shows the exact time of the event, as well as its duration and magnitude. The events can be categorized according to several attributes and selected for further root cause analysis.
If the trigger is activated, true valid (RMS) values, transients, and fast transients can be stored.
continuous recording The Fluke 1760 records the RMS values and corresponding minimum and maximum values for the following parameters:
- voltage
- electric current
- Electricity P, Q, S
- power factor
- kWh
- flicker
- disequilibrium
- frequency
- Harmonic/interharmonic continuity is accumulated using the following times: day, 10 minutes, free interval, e.g. 15 minutes, 2 hours <
trigger record effective value The accumulation time can be adjusted between 10 ms (1/2 cycle), 20 ms (1 cycle), 200 ms (10/12 cycles) or 3s (150/180 cycles).
RMS values, harmonics and interharmonics are calculated in synchronization with the power supply frequency.
Harmonics and interharmonics with a fundamental accumulation time of 200ms
oscillograph Sampling rate of 10.24 kHz for all 8 channels
fast transient Fast transient 1-4 FFT channels with selectable sampling rates from 100 kHz to 10 MHz
power signal (of an electrical device etc) Phase and N Lead, Voltage and Current
online mode Variable Refresh Rate. This feature allows users to verify meter settings and quickly navigate through oscilloscopes, transients and events.
General data
intrinsic uncertainty Please refer to the reference conditions, which provide a two-year guarantee
quality system Developed and manufactured according to ISO 9001: 2000
environmental conditions Operating temperature range 0 °C to +50 °C; 32 °F to +122 °F
Operating Temperature Range -20 °C to +50 °C; -4 °F to +122 °F
Storage temperature range 20 °C to +60 °C; -4 °F to 140 °F
reference temperature 23 °C ±2 K; 74 °F ±2 K
climatic scale B2 (IEC 654-1), -20°C to +50°C; -4°F to +122°F
Maximum working altitude 2000 m: max. 600 V CAT IV¹, power supply: 300 V CAT III 5000 m: max. 600 V CAT III¹, power supply: 300 V CAT II
1. Depending on the sensor
reference condition environmental temperature 23 °C ±2 K; 74 °F ±2 K
power supply 230 V ±10%
power frequency 50 Hz / 60 Hz
code Nominal input voltage indicated Udin
on average 10-minute intervals
housings Insulated, rugged plastic housing
Electromagnetic Compatibility (EMC) radiation standard Class A according to IEC/EN 61326-1
immunity IEC/EN 61326-1
power supply range (of scales or measuring equipment) AC: 83 V to 264 V, 45 to 65 Hz
DC: 100 V to 375 V
security level IEC/EN 61010-1 2nd edition
300 V CAT III
power wastage NiMH, 7.2 V, 2.7 hours
battery pack If the power supply fails, the internal battery will continue to supply power for up to 40 minutes. After that, or if the battery is depleted, the Fluke 1760 shuts down; when the supply voltage is restored, measurements can continue using the most recent previous settings. The battery can be replaced by the user.
monitor The Fluke 1760 is equipped with LEDs that indicate the status of each of the following: 8 channels, phase sequence, power (mains or battery), memory usage, time synchronization, and data transfer.
Power indicator
  • Long light: the power supply is normally powered.
  • Out: Power is supplied via the internal battery in the event of a power failure.
A 3-color indicator for each channel is used to indicate
  • overloaded state
  • underload condition
data memory 2 GB flash memory
memory mode biometrics
connector Ethernet (100MB/s), Windows® XP, 7 and 8 compatible, RS 232, external modem (via RS 232)
Baud rate for RS 232 9600 baud to 115K baud
Dimensions (H x W x D) 325 x 300 x 65 mm; 2.8 x 11.8 x 2.6 in
weights Approx. 4.9 kg; 10.8 lbs. (without accessories)
warranty period 2 years
Calibration interval 1 year for category A, 2 years for others.
signal conditioning
50 Hz System Range 50 Hz ±15% (42.5 Hz to 57.5 Hz)
60 Hz System Range 60 Hz ±15% (51 Hz to 69 Hz)
resolution (of a photo) 16ppm
50 Hz power supply frequency sampling frequency 10.24 kHz, sampling rate synchronized with power supply frequency.
Uncertainty of frequency measurements < 20 ppm
Uncertainty of the internal clock < 1s/day
Measurement interval Totalization of interval values according to IEC 61000-4-30 Class-A
Minimum, maximum 1/2 cycle, e.g. 10 ms RMS value (50 Hz)
transient Sample rate range of 100 kHz to 10 MHz per channel
harmonic (wave with frequency an integer multiple of the fundamental) Complies with IEC 61000-4-7:2002: 200 ms.
flicker Conforms to EN 61000-4-15:2003: 10 minutes (Pst), 2 hours (Plt)
Measurement input
Number of inputs 8 current-isolated inputs for voltage and current measurement.
Sensor Safety max. 600 V CAT IV (depending on sensor)
Basic security level 300 V CAT III
Rated Voltage (rms) 100 mV
Range (peak) 280 mV
Overload Capacity (rms) 1000 V (continuous)
Voltage Rise Rate 15 kV / µs max.
input resistance 1 MΩ
Input Capacitance 5 pF
Input filters Each channel is equipped with a passive low-pass filter, an anti-mixing filter and a 16-bit A/D converter. All channels are sampled in synchronization with a common quartz control clock pulse.
The filter prevents voltage transients and limits the rate of rise of the signal, reducing the high-frequency component, especially in the case of noise voltages exceeding half the A/D converter's sampling rate by 80 dB, and thus realizing very small measurement errors over a very large amplitude range. This is also effective under extreme operating conditions such as transient voltages at the converter output.
uncertainties
Uncertainty at reference conditions Includes voltage sensors with uncertainties according to IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz.
Sensor 1000 V 0.1% Udin = 480 V and 600 V P-N
Sensor 600 V 0.1% Udin = 230 V P-N
Inherent uncertainty of harmonics Class I according to EN 61000-4-7:2002
reference condition 23°C ± 2 K < 60 % rH; 74°F ± 2 K < 60 % rH
Warming up the instrument > 3 hours
Power supply: 100 V to 250 V AC
temperature drift 100 ppm / K
ageing < 0.05%/year
Common mode rejection ratio > 100 dB (at 50 Hz)
temperature drift Change in increase due to temperature: < 0.005 %/K
ageing Change in increase due to aging: < 0.04 %/year
noises Noise voltage, short-circuit input: < 40 µV
direct current (D.C.) ± (0.2% rdg + 0.1% sensor)

Model: Fluke 1760TR Three-Phase Power Quality Recorder

Fluke 1760TR

Topas Power Quality Recorder

With 8 input channels (4 current/4 voltage channels or 8 voltage channels)

Contains.

  • Internal flash memory 2 GB
  • PQ analysis software included on CD-ROM
  • Ethernet cable for network connection (1)
  • Cross-linked Ethernet cable for direct connection to PC (1)
  • Power Cables (1)
  • operation manual
  • grip
  • Fast transient analysis up to 10 MHz
  • 4 voltage probes (600 V for international settings; 1000 V for US settings)
  • 4 current probes (dual range flexible current probe 1000 A / 200 A AC)
  • GPS time synchronization receivers

Fluke 1760TR three-phase technical data [please login to download and view]

Expand More
Fluke 1760TR Three-Phase Power Quality RecorderFluke 1760TR Three-Phase Power Quality Recorder
¥999,999.00
Purchase of goods

Product consultation and purchase:18218718851

I already understand