DC High Voltage Test Probe P2010
DC High Voltage Test Probe P2010
DC High Voltage Test Probe P2010
DC High Voltage Test Probe P2010
DC High Voltage Test Probe P2010
DC High Voltage Test Probe P2010

● Realization of high voltage measurements up to CAT III 2000V
:: Safe measurement of megawatt-scale photovoltaic power plants without interrupting the grid
● Can be used with a corresponding HIOKI clamp meter or digital multimeter (DMM).

  • 22f8cd62defc50170169ae0c014c4a4a
    Why do you need CAT III 2000V measurements?

    In recent years, the increasing popularity of photovoltaic systems and electric vehicle batteries has created a whole new set of maintenance requirements, as has the demand for higher operating voltages. At the same time, the use of higher voltages poses greater safety risks.

    The CAT safety classification categorizes measurement locations by measurement category classes CAT II, CAT III, and CAT IV, based on the rated voltage between the lines, current capacity, and transient overvoltages at the measurement location. According to the international standard for the safety qualification of photovoltaic (PV) modules (IEC 61730-1), PV modules are classified as overvoltage CAT III and require measuring equipment capable of measuring CAT III.

    In this context, measuring instruments used for the maintenance of photovoltaic power plants must be able to withstand high voltages to ensure that they can be used safely. The use of instruments with the corresponding CAT safety rating helps to protect both the operator and the PV plant from serious accidents such as electric shocks and burn-outs.

    Currently, more and more systems are utilizing 1500 V photovoltaic power generation equipment, but as larger, more efficient systems come on line, there will be a need for instruments that can accommodate higher voltages in the future. Looking to the near future, the P2010 was created as a CAT III 2000 V compatible product.

  • 4fee4071c7b2b001a6cb120c0b336464
    Safer measurement of PV panels and PV devices

    High voltages up to 2000 V can be safely measured by connecting the P2010 to a HIOKI HIOKI clamp meter or digital multimeter (DMM).
    Function name: DC HIGH V PROBE mode

Basic parameters (accuracy guaranteed for 1 year)

Maximum input voltage (*1) DC 2000 V
*1: Between INPUT H - INPUT L, max. nominal voltage
Maximum rated voltage to ground 1000 V (Measurement category IV) Expected transient overvoltage 12000 V
2000 V (Measurement category III) Estimated transient overvoltage 15000 V
input resistance 20 MΩ ±5.0% (between INPUT H - INPUT L, when OUTPUT terminal is open)
overload protection DC 2200 V/AC 2200 V 1 minute (between INPUT H - INPUT L)
DC 600 V/AC 600 V 1 minute (between OUTPUT H - OUTPUT L)
OUTPUT terminal 4mm banana head
Operating temperature and humidity range Temperature: -25℃~65℃
Humidity:
-25℃~40℃:: 80% RH or less (no condensation)
40°C to 65°C: Linear reduction of the upper operating humidity limit from 40°C 80% RH to 65°C 25% RH (no condensation)
Storage temperature and humidity range -30°C to 70°C, 90% RH or less (no condensation)
Applicable norms EN 61010
attachment (email) Instruction manual × 1,, use of attention × 1

Combined accuracy with clamp meter and multimeter

model number Combined accuracy parameters
DT4261 Range 600.0 V: Combined accuracy ±0.8% rdg ±0.2 V
Range 2000 V: Combined accuracy ±0.81 TP3T rdg ±5 V
CM4141-50 Range 600.0 V: Combined accuracy ±1.01 TP3T rdg ±0.3 V
Range 2000 V: Combined accuracy ±1.01 TP3T rdg ±3 V
CM4371-50
CM4373-50
CM4375-50
DT4281 Range 60.000 V: Combined accuracy ±0.8% rdg ±0.002 V (output ratio 1/10)
Range 600.00 V: Combined accuracy ±0.81 TP3T rdg ±0.02 V (output ratio 1/10)
DT4282
DT4252 Range 60.00 V: Combined accuracy ±1.21 TP3T rdg ±0.05 V (output ratio 1/10)
Range 600.0 V: Combined accuracy ±1.21 TP3T rdg ±0.5 V (output ratio 1/10)
DT4253
DT4255 Range 60.00 V: Combined accuracy ±1.21 TP3T rdg ±0.03 V (output ratio 1/10)
Range 600.0 V: Combined accuracy ±1.21 TP3T rdg ±0.3 V (output ratio 1/10)
DT4256